EN
banner

1 DSHCI-100HYBRID  DSHCI-112HYBRID
2 DSHCI-100HYBRID  DSHCI-112HYBRID
3 DSHCI-100HYBRID  DSHCI-112HYBRID
1 DSHCI-100HYBRID  DSHCI-112HYBRID
2 DSHCI-100HYBRID  DSHCI-112HYBRID
3 DSHCI-100HYBRID  DSHCI-112HYBRID
Application scenarios
家储

HZCI Series-(Air Cooling)

DSHCI-100HYBRID / DSHCI-112HYBRID

COMMERCIAL AND INDUSTRIAL ESS

Parameter
System Parameters
DC Battery Parameters
Battery Rated Energy (KWh)100/112
Battery Rated Voltage (V)358.4
Battery Voltage Range (V)324.8 - 397.6
Battery TypeLFP
Battery Energy (Ah)280/314Ah
Battery Life Cycle6,000 Cycles (0.5C, 5%~95%DOD, 80%SOH)
Battery Standard Charge/Discharge Rate (C)

0.5

Battery Pack Series And Parallel1P112S
Module Cooling MethodAir Cooling
AC Parameters
Rated AC Power (KW)50
Maximum Power (KW)55
Maximum Current (A)200
Rated AC Voltage (V)400
AC Voltage Range±15%
Rated AC Frequency (Hz)50/60
Wiring Method3P+N+PE
Current Distortion Rate THDI< 3% (Rated Power)
Power Factor≥0.99/-1~1
Voltage Total Harmonic Distortion THDU< 3% (Linear Load)
PCS Cooling MethodAir Cooling
Maximum Efficiency97.80%


Energy Cycle Efficiency≥ 90 %
Protection LevelIP54
Corrosion Resistance LevelC3 is the default, C4/C5 are optional
Fire FightingAerosol/Perfluorohexanone (Optional)
Isolation MethodNot Isolated (Transformer Optional)
Relative Humidity0~95% (Non-condensing)
Ambient Temperature-30℃ ~ 55℃ (Derating Above 45℃)
Altitude<3000m ( Derating Applies Over 2000m )
BMS CommunicationCAN
EMS Communications4G/CAN/RS485
Dimensions (mm)540 * 1200 * 2300
Weight (T)2.6
Annual Decay Rate<3%
Warranty5 years
Battery, EMS, BMS, PCS, DCDC, STS all In one cabinet support on/off-grid system
PV Parmater
Recommended Max. PV Array (KW)100
Max. Input Voltage (V)1000
Rated Voltage (V)600
MPPT Voltage Range (V)150~850

Features

Downloads